CTTI Heat Exchangers / IRAN
  • images/de/1.jpg|Drift Eliminator profile type TAP160
  • images/de/2.jpg|Drift Eliminator chamber type TEP-TEC 130
Leftright
/

GEA 2H Drift Eliminators



Reduce water loss and emissions

In all different types of cooling towers, drift eliminators are used to reduce the loss of water and emissions. Above the water distribution and the cooling fills, a layer of drift eliminators is installed for this purpose. It catches the water drops which are carried away with the air flow and redirects them into the cooling water circuit.

GEA 2H Drift Eliminators are available in two different types. The profile (TAP 160) is mostly used in bigger, the chamber types (TEP 130 and TEC 130) in smaller cooling towers.


  • Technical Data
Type TEP 130 TEC 130 TAP 160 with Spacer TAS 033
Material PP PVC PP
Max. length / width (mm) 2400 / 700 2400 / 800 6000 / 330
Height (mm) 125 / 250 125 / 250 160
Drift loss* (%) > 0.0007 - 0.0005 > 0.0007 - 0.0005 > 0.0012 - 0.0006
Contin. operation temp. / Max. operation temp. (C°) 70 / 80 (short time) 55 / 60 (short time) 70 / 80 (short time)
Max. face velocity (m/s) 4.5 4.5 40
Drag coefficient 2.2 2.2 2.6
Pitch (mm) 18 18 33 / 38
Max. distance between supports (mm) 1000 1000 1000