Modular Cooling Towers - GEA TCO / RCO Systems
Open Loop Cooling Towers
TCO / RCO systems combine a high cooling capacity with low noise fan. The modules are supplied ready to use and they are easy to adjust to cooling require¬ments and the available space, whether they are used singly or in series. The cooling performance of these cooling towers is optimal and operation is problem free. With a 95%+ saving in water, the efficient TCO / RCO systems are the best choice for man and his environment.
The effect of counter flow
TCO RCO open loop cooling towers work on the principle of counter flow. This means that the water flows down while the air is pushed upwards by a radial fan. As the water flows further through the system, the air it encounters is fresher, in other words cooler and less satu¬rated with moisture.
Counter flow cooling towers can approach the wet bulb tempe¬rature better compared with cross flow cooling towers.
The security of quality
GEA designs and manufactures cooling towers with long life times and minimal maintenance needs. This is achieved through the materials used - galvanized steel withSORABOND® epoxy coating - the sound design and the experience of our engineers. This range of high quality GEA products is delivered fully assembled and ready to use.
- RCO 10 - RCO 27
- RCO 31 - RCO 55
Type |
RCO10 |
RCO18 |
RCO21 |
RCO27 |
Wet surface (m2) |
0.8 |
1.5 |
2.9 |
4.3 |
Q min (m3/h) |
6 |
11 |
20 |
30 |
Q max (m3/h) |
28 |
53 |
102 |
151 |
Lenght (mm) |
940 |
1740 |
1740 |
2540 |
Width (mm) |
940 |
940 |
1740 |
1740 |
Height (mm) |
3075 |
2775 |
3055 |
3055 |
Weight empty (kg) |
270 |
310 |
670 |
900 |
Weight operational (kg) |
540 |
690 |
1780 |
2690 |
Number of engine(s) |
direct |
direct |
direct |
direct |
Type |
RCO31 |
RCO36 |
RCO42 |
RCO55 |
Wet surface (m2) |
6.6 |
8.3 |
10.9 |
10.9 |
Q min (m3/h) |
44 |
58 |
76 |
76 |
Q max (m3/h) |
221 |
291 |
382 |
382 |
Lenght (mm) |
2540 |
3340 |
3340 |
3340 |
Width (mm) |
2540 |
2540 |
3340 |
3340 |
Height (mm) |
4050 |
4175 |
4575 |
4575 |
Weight empty (kg) |
1260 |
1610 |
2090 |
2090 |
Weight operational (kg) |
4050 |
5410 |
7230 |
7230 |
Number of engine(s) |
geared motor |
geared motor |
geared motor |
geared motor |