TUBEdek® Lamella Clarifiers (Tube Settlers)
Cost savings by smaller tanks
GEA 2H TUBEdek® Lamella Clarifiers, also called tube settlers, are used for solids removal (sedimentation processes) in water and sewage treatment. GEA 2H TUBEdek® can be used in rectangular and in circular tanks.
Sludge, sand and silts in surface water, chemical precipitation and flocculation form solids which have to be removed. The most economic process to remove this pollution is parallel plate sedimentation.
GEA 2H TUBEdek® lamella clarifiers base on this physical principle. They consist of single profiles, which are assembled to a module forming several adjacent tubes and multiple sedimentation planes. This design increases the sedimentation area by a factor of 6 to 15 per square meter footprint. Using GEA 2H TUBEdek® tube settlers therefore decreases costs by being able to build smaller tanks.
Flexibility for all different applications
GEA’s different tube settler types enable optimized sewage treatment processes. By choosing different tube lengths and heights and by varying the inclination angle, GEA 2H TUBEdek® settlers can be adjusted to all kinds of process requirements and tank geometry.
Engineering support by GEA
Please use GEA’s long experience and application know-how and ask for support in designing your clarifier or sedimentation tank.
- TUBEdek® Typical Applications
- Technical data
Type |
FS 41.84 |
FS 41.62 |
FS 41.50 FS 42.50 |
KLP 638 |
Potable and process water |
- |
Highly loaded surface water |
Surface water Groundwater Filter backwash water |
Low solids load polishing |
Waste water |
Primary sedimentation Activated sludge with low sludge volume |
Stormwater Humus tanks behind fixed film processes |
Aquaculture Humus tanks behind fixed film processes Flocculated water Stormwater |
Aquaculture Polishing |
Type |
FS 41.84 |
FS 41.62 |
FS 41.50 |
FS 42.50 |
KLP 638 |
Material |
PVC PPTV |
PPTV |
PVC PPTV |
PPTV |
PPTV |
Sedimentation area / Slope 60° (m2/m3) |
6.25 |
8 |
11 |
12 |
15 |
Sedimentation area / Slope 55° (m2/m3) |
7 |
9 |
13 |
13.5 |
- |
Vertical module height (H/mm) |
700-2000 |
On request |
500-2000 |
500-1000 |
610 |
Standard module height (H/mm) |
1000/1500 |
1000 |
1000 |
1000 |
610 |
Lamella pitch (mm) |
83 (+/-1) |
64 (+/-1) |
45 (+/-1) |
43 (+/-1) |
33 (average) |
Hydraulic radius (cm) |
2.6 |
2.5 |
1.7 |
1.6 |
1.7 |
Contin. operation temp. Max operation temp. PVC (°C) |
55
60 (short term) |
- |
55
60 (short term) |
- |
- |
Contin. operation temp. Max operation temp. PPTV (°C) |
70 80 (short term) |
70 80 (short term) |
70 80 (short term) |
70 80 (short term) |
70 80 (short term) |